Printed in U.S.A. 8-08 © Copyright 2008 TAC All Rights Reserved. F-18097-8
TP-8101, TP-8102, TP-8103
These self-contained room temperature controllers conserve
energy in heating and/or cooling applications requiring a
single setpoint adjustment. See Table-1 for particular
characteristics.
The heating and cooling equipment is precisely controlled
from a single 1000 ohm Balco sensor operating through a
single controller for heating and/or cooling. The controller
provides a proportional output to control TAC System 8000
controlled devices for control of valves, dampers, electric
heat, DX coils, etc.
TP-8124, TP-8125
These self-contained room controllers conserve energy in
heating and/or cooling equipment in applications requiring
heating and cooling setpoint adjustment.
See Table-1 for particular characteristics.
The heating and cooling equipment is precisely controlled
from a single 1000 ohm Balco sensor operating through
independent heating and cooling controllers. These
controllers provide proportional outputs to control TAC
System 8000 controlled devices for control of valves,
dampers, electric heat, DX coils, etc. The heating output
(OP1 to COM) can be programmed for direct-acting or
reverse-acting operation. The cooling output (OP2 to COM)
provides a direct-acting output only.
Table-1
Part Number
Dial
Marking
Control
Dial Range
Throttling
Range for 3
Vdc Output
Change
Input
Voltage
Output
Voltage
Control Action
Wiring
Connections
Number of
Controlled
Devices
TP-8101 °F & °C55-85°F
2, 3, 6 and
20°F Factory
Set 3°F By
Jumper/Pins
20 Vdc
13 mA
2-15 Vdc
or
15-2 Vdc
Factory Set
Direct-acting
Jumper
Terminal 4 to 5
For
Reverse-acting
Jumper
Terminal 4 to 3
3 Color-coded
Pigtail Leads
Terminals for
Options See
Figure 2
6
TAC System
8000
Devices or 2
MP-5200
Series
Actuators
TP-8101-116 °C 13-29°C
TP-8102 °F & °C
7-24°C
(45-75°F)
TP-8103 °F & °C
24-41°C
(75-105°F)
TP-8124 Dual
Setpoints
°F & °C
Heating
7-24°C
(45-75°F)
cooling
21-38
°C
(70-100°F)
Heating and
Cooling
2-10°F
Independently
Adj.
Factory Set
3°F
20 Vdc
23 mA
Heat 2-15 Vdc
or
15-2 Vdc
Cool
2-15 Vdc
Heating Factory
Set
Reverse-acting
Jumper J7
to pin B for
Direct-acting
Cooling
Direct-acting
only
Coded
Terminals
see Figure 3
6
TAC System
8000
Devices or 2
MP-5200
Series
Actuators in
both Heating
and Cooling
TP-8125
Dual
Setpoints
°F & °C
Heating
7-24°C
(45-75°F)
Cooling
24-41°C
(75-105°F)
TP-8101, TP-8102, TP-8103,
TP-8124, TP-8125
Electronic, Proportional Controlling
Thermostats
General Instructions
9
0
8
0
7
0
6
0
5
0
TP-8101,
TP-8102,
TP-8103
Single Setpoint
Adjustment
TP-8124
& TP-8125
Dual
Setpoint
Adjustment
Przeglądanie stron 0
1 2 3 4 5 6 ... 11 12

Podsumowanie treści

Strona 1 - TP-8124, TP-8125

Printed in U.S.A. 8-08 © Copyright 2008 TAC All Rights Reserved. F-18097-8TP-8101, TP-8102, TP-8103These self-contained room temperature controllers c

Strona 2

10 © Copyright 2008 TAC All Rights Reserved F-18097-8Figure-15 TP-8101, TP-8102, and TP-8103 with Remote Setpoint and/or Selective Ratio Discharge Sen

Strona 3 - CONTROLLER

F-18097-8 © Copyright 2008 TAC All Rights Reserved 11Figure-17 Tp-8101, TP-8102, and TP-8103 with Remote Setpoint and/or Selective Ratio Discharge Sen

Strona 4 - One or No

Copyright 2007, TACAll brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within thi

Strona 5 - TP-8124 and TP-8125

2 © Copyright 2008 TAC All Rights Reserved. F-18097-8Features1. TP-8124 meets ASHRAE 90-75 and DOE requirements. TP-8125 meets DOD requirements.2. Hea

Strona 6

F-18097-8 © Copyright 2008 TAC All Rights Reserved. 3WIRING OF CONTROLLED DEVICES TO CONTROLLERTypes of controlled devices and their power supplies:1.

Strona 7

4 © Copyright 2008 TAC All Rights Reserved. F-18097-8Figure-5 TP-8101, TP-8102, and TP-8103 Typical Wiring with MP-52xx Actuators.Figure-6 TP-8124 and

Strona 8

F-18097-8 © Copyright 2008 TAC All Rights Reserved. 5Figure-7 TP-8124 and TP-8125 Typical Wiring with Two MP-52xx Actuators.ADJUSTMENTSTP-8101, TP-810

Strona 9

6 © Copyright 2008 TAC All Rights Reserved. F-18097-83. The Temperature Deadband between heating and cooling is the difference in SPB and SPA settings

Strona 10 - Reverse-Acting Output Only

F-18097-8 © Copyright 2008 TAC All Rights Reserved. 72. If room temperature is 75°F or greater:a. Connect VOM internally to OP2 (+) and COM (-). See F

Strona 11

8 © Copyright 2008 TAC All Rights Reserved. F-18097-8Figure-12 TP-8124 and TP-8125 Block Diagram.OPTIONSTP-8101, TP-8102, TP-8103(TP-8124 and TP-8125

Strona 12 - MAINTENANCE

F-18097-8 © Copyright 2008 TAC All Rights Reserved. 9Figure-13 TP-8101, TP-8102, and TP-8103 with Single Pole Double Throw (SPDT) Winter-Summer Switch